Instruction Manual
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013 81
PowerMonitor 1000 Data Tables Appendix A
4 40505 Off Peak Days 65 0…127 •••This bit map field selects the off peak days.
OFF-PEAK days have only one rate for billing.
Bit0= Sunday
Bit1= Monday
Bit2= Tuesday
Bit3= Wednesday
Bit4= Thursday
Bit5= Friday
Bit6= Saturday
Saturday and Sunday are default Off Peak
days.
5 40506 MID Peak AM
Hours
1792 0…
4095
•••This bit map selects any AM hours that are
designated as MID Peak. Example: The hours
from 8 AM to 11AM is designated as bit 8
through bit 10 = 1792d.
Bit0= 12 AM…1 AM
Bit1= 1 AM…2 AM
Bit2= 2 AM…3 AM
…
…
Bit11= 11AM…12 AM
Default is 8 AM…11 AM
6 40507 MID Peak PM
Hours
120 0…
4095
•••This bit map selects any PM hours that are
designated as MID Peak. Example: The hours
from 3 PM to 7 PM is designated as bit 3
through bit 6 = 120d.
Bit0= 12 PM…1 PM
Bit1= 1 PM…2 PM
Bit2= 2 PM…3 PM
…
…
Bit11= 11PM…12 PM
Default is 3 PM…7 PM
7 40508 ON Peak AM
Hours
2048 0…
4095
•••This bit map selects any AM hours that are
designated as ON Peak. Example: The hours
from 11AM to 12 PM is designated as bit 11
= 2048d.
Bit0= 12 AM…1 AM
Bit1= 1 AM…2 AM
Bit2= 2 AM…3 AM
…
Bit11= 11AM…12 AM
Default is 11AM
8 40509 ON Peak PM
hours
7 0…4095 •••This bit map selects any PM hours that are
designated as ON Peak. Example: The hours
from 12 PM to 3 PM is designated as bit 0
through bit 2 = 7d
Bit0= 12 PM…1 PM
Bit1= 1 PM…2 PM
Bit2= 2 PM…3 PM
…
Bit11= 11PM…12 PM
Default is 12 PM…3 PM
Table 16 - Log Configuration
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description