PowerMonitor 1000 Data Tables Appendix A
Table 19 - Log Request Table Parameters
CSP File No. N17
CIP Instance 10
No. of Elements 11
No. of Words 11
Data Type Integer
Data Access Read/Write
Table 20 - Log Request Table
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description
0 40701 Selected Log 0 0…5 •••••Selects the log that information is returned
from. Once a single request has been
made the auto return feature will bring
back successive records each time the log
is read. Some logs support individual
record requests.
1 = Unit Status Log
2 = Min/Max Log
3 = Energy Log
4 = Load Factor Log
5 = Time of Use Log kWh
6 = Time of Use Log kVAR
7 = Time of Use Log kVA
If your catalog number does not support
the requested log item the power monitor
will ignore the request.
1 40702 Chronology of
Auto Return Data
101•••••The date chronology of the returned
records.
0 = Reverse direction
1 = Forward direction
2 40703 The Min/Max
record to be
returned
0 0…35
0…31
0…15
•• Selects the Min/Max record number to be
returned. See the table for Min/Max
record list.
0 = Use incremental return and the
chronology selected.
EM3 = 1…35
TR2 = 1…31
TR1 = 1…15
3 40704 Number of Unit
Status Records
- 1…50 •••••On a read of this table the value of this
parameter is the number of Unit Status
Records available. This log is only returned
using the incremental return method.
4 40705 Number of Energy
Log Records
-0
17,280
•••On a read of this table the value of this
parameter is the number of Energy Log
Records available.