Rockwell Automation Publication 1408-UM001D-EN-P - September 2013 87
PowerMonitor 1000 Data Tables Appendix A
Table 21 - Controller Interface Table Parameters
CSP File No. N18
CIP Instance 11
Applies to EM2, EM3 only
No. of Elements 8
No. of Words 8
Data Type Integer
Data Access Write
Table 22 - Controller Interface Table
Element
No.
Modbus
Address
Element Name Default
Value
Range Description
0 40801 Password 0 0…9999 When writing the complete table this parameter allows the input data to be
accepted. When writing a single parameter the separate password table
should be used. Returns -1 on a read.
1 40802 Controller
Command Word
0 0…1 Bit 0 = When this bit is written to the power monitor it signals the end of the
demand period. The power monitor resets the bit to 0 and sends the end of
demand broadcast to all of the slaves configured for the master/slave
demand system. The power monitor must be configured as a Master for
external demand pulse input.
Bit 1…15 = Reserved
2 40803 Reserved 0 0 Reserved for future use.
3 40804 Reserved 0 0 Reserved for future use.
4 40805 Reserved 0 0 Reserved for future use.
5 40806 Reserved 0 0 Reserved for future use.
6 40807 Reserved 0 0 Reserved for future use.
7 40808 Reserved 0 0 Reserved for future use.