Instruction Manual
Rockwell Automation Publication 1408-UM001D-EN-P - September 2013 89
PowerMonitor 1000 Data Tables Appendix A
Table 25 - Wiring Diagnostics Results Parameters
CSP File No. F20
CIP Instance 13
No. of Elements 21
No. of Words 42
Data Type Float
Data Access Read
Table 26 - Wiring Diagnostics Results
Element
No.
Modbus
Address
Element Name Units Range
TR1
TR2
EM1
EM2
EM3
Description
0 30101-2 Wiring Status 0…5 •••••This is the overall status of the wiring
diagnostic test.
0 = Pass
1 = Failed
2 = Input Level Low
3 = Disabled
4 = Waiting Command
5 = Out of range
1 30103-4 Voltage Input
Missing
-1…123 •••••Reports on all three phases.
-1 = Test not run.
0 = Test passed.
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing
2 30105-6 Voltage Input
Inverted
-1…123 •••••Reports on all three phases.
-1 = Test not run.
0 = Test passed.
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted
3 30107-8 Current Input
Missing
-1…123 •••••Reports on all three phases.
-1 = Test not run.
0 = Test passed.
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing