Table 29 - Power Results Parameters
CSP File No. F22
CIP Instance 15
No. of Elements 17
No. of Words 34
Data Type Float
Data Access Read
Table 30 - Power Results
Element
No.
Modbus
Address
Element Name Range
TR1
TR2
EM1
EM2
EM3
Description
0 30301-2 L1 True Power Factor -100.0…+100.0 ••Percent ratio between power and
apparent power. The value is signed
to (+) leading and (-) lagging.
1 30303-4 L2 True Power Factor -100.0…+100.0 ••
2 30305-6 L3 True Power Factor -100.0…+100.0 ••
3 30307-8 3 Phase True Power
Factor
-100.0…+100.0 ••
4 30309-10 L1 kWatts +/- 0.000…9,999,999 ••Line 1 kWatts
5 30311-12 L2 kWatts +/- 0.000…9,999,999 ••Line 2 kWatts
6 30313-14 L3 kWatts +/- 0.000…9,999,999 ••Line 3 kWatts
7 30315-16 Total kWatts +/- 0.000…9,999,999 ••Total kWatts
8 30317-18 L1 kVAR +/- 0.000…9,999,999 ••Line 1 kVAR
9 30319-20 L2 kVAR +/- 0.000…9,999,999 ••Line 2 kVAR
10 30321-22 L3 kVAR +/- 0.000…9,999,999 ••Line 3 kVAR
11 30323-24 Total kVAR +/- 0.000…9,999,999 ••Total kVAR
12 30325-26 L1 kVA 0.000…9,999,999 ••Line 1 kVA
13 30327-28 L2 kVA 0.000…9,999,999 ••Line 2 kVA
14 30329-30 L3 kVA 0.000…9,999,999 ••Line 3 kVA
15 30331-32 Total kVA 0.000…9,999,999 ••Total kVA
16 30333-34 Metering Iteration 0…9,999,999 ••Increments by 1 for each new
metering calculation.
IMPORTANT
Only total power values are returned in delta wiring modes.
Zeroes are returned for individual phase values.