Instruction Manual
98 Rockwell Automation Publication 1408-UM001D-EN-P - September 2013
Appendix A PowerMonitor 1000 Data Tables
Table 38 - Energy Log Results Parameters
CSP File No. F26
CIP Instance 19
No. of Elements 21
No. of Words 42
Data Type Float
Data Access Read
Table 39 - Energy Log Results
Element
No.
Modbus
Address
Element Name Range
TR1
TR2
EM1
EM2
EM3
Description
0 30701-2 Internal Record
Identifier.
•••
1 30703-4 Timestamp Year of
record
- •••The date and time when the
record was recorded.
2 30705-6 Timestamp Month/
Day
- •••
3 30707-8 Timestamp Hour/
Minute
- •••
4 30709-10 Timestamp Seconds/
Hundredths
- •••
5 30711-12 Status 1 Count xM 0…9,999,999 •••Status 1 Count times 1,000,000
6 30713-14 Status 1 Count x1 0…999,999 •••Status 1 count times 1
7 30715-16 Status 2 Count xM 0…9,999,999 •••Status 2 Count times 1,000,000
8 30717-18 Status 2 Count x1 0…999,999 •••Status 2 count times 1
9 30719-20 GWh Net +/- 0…9,999,999 •••Net gigawatt hours
10 30721-22 kWatth Net +/- 0.000…999,999 •••Net kilowatt hours
11 30723-24 GVARH Net +/- 0…9,999,999 ••Net gigaVAR hours
12 30725-26 kVARh Net +/- 0.000…999,999 ••Net kiloVAR hours
13 30727-28 GVAh Net 0…9,999,999 ••Net gigaVA hours
14 30729-30 kVAh Net 0.000…999,999 ••Net kiloVA hours
15 30731-32 kWatt Demand +/- 0.000…9,999,999 ••The average real power during
the last demand period.
16 30733-34 kVAR Demand +/- 0.000…9,999,999 ••The average reactive power
during the last demand period.
17 30735-36 kVA Demand 0.000…9,999,999 ••The average apparent power
during the last demand period.
18 30737-38 Demand PF -100.0…+100.0 ••The average demand for PF during
the last demand period.
19 30739-40 Reserved 0 • • Reserved for future use.
20 30741-42 Reserved 0 • • Reserved for future use.