Reading Logs
You can perform explicit messages to read data from log records in
the power monitor.
For information on setting up explicit messages to the power monitor,
please refer to Explicit Message Setup – Examples
on page 17.
The following logs can be read into a controller depending on the
logs supported by your power monitor.
Unit Status Log
Min/Max Log
Energy Log
Load Factor Log
Time of Use Log kWh
Time of Use Log kVAR
Time of Use Log kVA
Please refer to Appendix
A for the data table address of the specific
log you are requesting.
Log Data Table Methodology
The log data tables only hold one record instance for a specific log.
Successive reads of the data table return a successive record instance
for that log. By writing to specific configuration elements in the Log
Request Table data table, you can configure the log to return in a
forward or reverse direction. You can also configure the log to return
a specific record for all logs except the Unit Status Log, and Energy
Log.
Refer to
Log Request Table on page 64 for more information.