User Manual
Publication 1408-UM001B-EN-P - May 2008 41
SCADA Applications Chapter 5
Reading the User Configured Table as Connected Instance 1
The following example illustrates the steps required to set up an I/O
connection between a Logix controller and the user configured
Instance 1. The example uses a CompactLogix controller and
RSLogix 5000 software.
Follow these steps to configure the connection.
1. Open an offline project in RSLogix 5000 software.
2. Open the Ethernet network interface and select the Ethernet
network.
3. Add a new module and choose Generic Ethernet Module from
the Communications group.
4. Configure the properties of the new module and click OK.
Parameter Choice
Name Your choice of name
Comm Format Input Data - REAL
IP Address The IP address of your power monitor
Input Assembly Instance 1; Size 16 (32-bit)
Output Assembly Instance 2
Configuration Assembly Instance 3; Size 0
Open Module Properties Leave checked