Powermonitor 1000 Data Tables Appendix A
11 40123-24 KYZ Pulse
Duration
Setting
250 ms 0 or
50…1000
•••Set as 50…1000 to indicate the duration
of the pulse in milliseconds, or set to 0 for
KYZ-style transition output. (Toggle)
The value for delay is rounded off to the
nearest 10ms internally during this
function.
12 40125-26 Status Input
1 Input Scale
11
1,000,000
•••When a status pulse is received the count
is increased by the scale factor. Input
pulse * input scale added to total status
count.
13 40127-28 Status Input
2 Input Scale
11
1,000,000
•••When a status pulse is received the count
is increased by the scale factor. Input
pulse * input scale added to total status
count.
14 40129-30 Demand
Source
003 ••When item Demand Broadcast Master
Select of the ethernet table is set to
master a selection of 0 through 2 sets the
type of master input. In this case item 3 is
ignored. When the Demand Broadcast
Master Select of the ethernet table is set
to slave then any of these inputs can set
the end of the demand period. Selections
of 0 through 2 can be selected for RS485
units.
0 = Internal Timer
1 = Status Input 2
2 = Controller Command
3 = Ethernet Demand Broadcast
Selection 3 can only be programmed when
the Ethernet option is installed.
15 40131-32 Demand
Period
Length
15 min 0…99 ••Specifies the desired period for demand
calculations. When set to 0 there are no
projected demand calculations. If the
internal timer is selected a setting of 0
turns the demand function off.
16 40133-34 Number of
Demand
Periods
1115 ••Specifies the number of demand periods
to average for demand measurement.