User Manual

52 Publication 1408-UM001B-EN-P - May 2008
Appendix A Powermonitor 1000 Data Tables
5 40206 Data Format 0 0…2
(2 for
DH485)
Parity, number of data bits, number of stop bits
0 = No parity, 8 data bits, 1 stop bit
1 = Odd parity, 8 data bits, 1 stop bit
2 = Even parity, 8 data bits, 1 stop bit
6 40207 Inter Character
Timeout
00
6553
Specifies the minimum delay between characters that indicates the
end of a message packet for Modbus protocol. 0 = 3.5 character
times in default. The unit is ms.
8 40208 Maximum Node
Address
3 1…31 Specifies the maximum node address on a DH485 network.
9 40209 Reserved 0 0 Reserved for future use.
Serial RS-485 Port Configuration
Element
No.
Modbus
Address
Element Name Default
Value
Range Description
Ethernet Configuration Parameters
CSP File No. N13
CIP Instance 6
No. of Elements 23
No. of Words 23
Data Type Integer
Data Access Read/Write
Ethernet Configuration
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description
0 40301 Password 0 0…9999 •••••When writing the complete table this
parameter allows the input data to be
accepted. When writing a single
parameter the separate password table
should be used. Returns -1 on a read.
1 40302 IP Address Byte a
(aaa.xxx.xxx.xxx)
192 0…255 •••••The 1st Octet of the Static IP Address.
2 40303 IP Address Byte b
(xxx.bbb.xxx.xxx)
168 0…255 •••••The 2nd Octet of the Static IP Address.
3 40304 IP Address Byte c
(xxx.xxx.ccc.xxx)
254 0…255 •••••The 3rd Octet of the Static IP Address.
4 40305 IP Address Byte d
(xxx.xxx.ddd.xxx)
Unit ID 0…255 •••••The 4th Octet of the Static IP Address.