Powermonitor 1000 Data Tables Appendix A
Date and Time Configuration Parameters
CSP File No. N14
CIP Instance 7
Applies to All models
No. of Elements 8
No. of Words 8
Data Type Integer
Data Access Read/Write
Date and Time Configuration
Element
No.
Modbus
Address
Element Name Default
Value
Range Description
0 40401 Password 0 0…9999 When writing the complete table this parameter allows the
input data to be accepted. When writing a single parameter the
separate password table should be used. Returns -1 on a read.
1 40402 Date: Year 2005 2001…
2100
The range is from 2001… 2100. A write sets the current year.
2 40403 Date: Month 1 1…12 A write sets the current month.
A read returns current month.
1=January, 2=February,…12=December
3 40404 Date: Day 1 1…31 A write sets the current day of the month.
A reads returns the current day of the month.
The internal real-time clock adjusts the date for leap-year.
4 40405 Time: Hour 0 0…23 A write sets the current hour.
A read returns the current hour.
0=12am, 1=1am,…23=11pm
The internal real-time clock does not adjust for daylight savings
time.
5 40406 Time: Minute 0 0…59 A write sets the current minutes.
A read returns the current minutes.
6 40407 Time: Seconds 0 0…59 A write sets the current seconds.
A read returns the current seconds.
7 40408 Time: Hundredths 0 0…99 Set this element to 0 for writes. Returns hundredths of a second
on read.