58 Publication 1408-UM001B-EN-P - May 2008
Appendix A Powermonitor 1000 Data Tables
Log Configuration Parameters
CSP File No. N15
CIP Instance 8
No. of Elements 12
No. of Words 12
Data Type Integer
Data Access Read/Write
Log Configuration
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description
0 40501 Password 0 0…
9999
•••When writing the complete table this
parameter allows the input data to be
accepted. When writing a single
parameter the separate password table
should be used. Returns -1 on a read.
1 40502 Energy Log
Interval
15 min -1…60 •••Selects how often a record is logged
(minutes). A value of 0 disables periodic
logging of records. A value of –1 causes
logging of records to be synchronized to
the end of the demand interval.
2 40503 Energy Log
Mode
101 •••This parameter set the action of the log
once is has filled to capacity. Setting the
option to 0 allows the log to fill but stops
at the end. Option 1 lets the log fill and
then oldest records are deleted and
replaced with new records.
0 = Fill and Stop
1 = Overwrite, When the log is filled new
records replace the oldest records.
3 40504 Time of Use Log
Auto Log
Setting
31 0…31 •••Automatically stores the current record
for the month replacing the oldest record
if the log is full. The log holds 12 months
plus the current record.
0 = Disables the auto clear feature.
1 = Store and clear the table on the 1st
day of each month.
2 = 2nd Day
3 = 3rd day
29…31 = Store and clear table at the
last day of the month.