Powermonitor 1000 Data Tables Appendix A
4 40505 Off Peak Days 65 0…127 •••This bit map field selects the off peak
days. OFF-PEAK days have only one rate
for billing.
Bit0= Sunday
Bit1= Monday
Bit2= Tuesday
Bit3= Wednesday
Bit4= Thursday
Bit5= Friday
Bit6= Saturday
Saturday and Sunday are default Off
Peak days.
5 40506 MID Peak AM
Hours
1792 0…
4095
•••This bit map selects any AM hours that
are designated as MID Peak. Example:
The hours from 8 AM to 11AM is
designated as bit 8 through bit 10 =
1792d.
Bit0= 12 AM…1 AM
Bit1= 1 AM…2 AM
Bit2= 2 AM…3 AM
Bit11= 11AM…12 AM
Default is 8 AM…11 AM
6 40507 MID Peak PM
Hours
120 0…
4095
•••This bit map selects any PM hours that
are designated as MID Peak. Example:
The hours from 3 PM to 7 PM is
designated as bit 3 through bit 6 = 120d.
Bit0= 12 PM…1 PM
Bit1= 1 PM…2 PM
Bit2= 2 PM…3 PM
Bit11= 11PM…12 PM
Default is 3 PM…7 PM
7 40508 ON Peak AM
Hours
2048 0…
4095
•••This bit map selects any AM hours that
are designated as ON Peak. Example:
The hours from 11AM to 12 PM is
designated as bit 11 = 2048d.
Bit0= 12 AM…1 AM
Bit1= 1 AM…2 AM
Bit2= 2 AM…3 AM
Bit11= 11AM…12 AM
Default is 11AM
Log Configuration
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description