User Manual
60 Publication 1408-UM001B-EN-P - May 2008
Appendix A Powermonitor 1000 Data Tables
8 40509 ON Peak PM
hours
7 0…409
5
•••This bit map selects any PM hours that
are designated as ON Peak. Example:
The hours from 12 PM to 3 PM is
designated as bit 0 through bit 2 = 7d
Bit0= 12 PM…1 PM
Bit1= 1 PM…2 PM
Bit2= 2 PM…3 PM
…
Bit11= 11PM…12 PM
Default is 12 PM…3 PM
9 40510 Load Factor log
Auto Log
Setting
31 0…31 •••Automatically stores the current peak,
average, and load factor results as a
record in the non-volatile load factor log
and resets the log at the specified day of
the month.
0 = Disables the auto clear feature.
1 = Store and clear the table on the 1st
day of each month.
2 = 2nd Day
3 = 3rd day
…
29…31 = Store and clear table at the
last day of the month.
10 40511 Reserved 0 0 • • • • • Reserved for future use.
11 40512 Reserved 0 0 • • • • • Reserved for future use.
Log Configuration
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description
Command Table Parameters
CSP File No. F16
CIP Instance 9
No. of Elements 22
No. of Words 44
Data Type Float
Data Access Write