62 Publication 1408-UM001B-EN-P - May 2008
Appendix A Powermonitor 1000 Data Tables
3 40607-8 Clear Single
Min/Max
Records
0 0…35
0…31
0…19
•• When setting the Min/Max Clear bit this
value can be sent to specify a single
parameter. If clearing all values this is
not required.
EM3 = 0…35
TR2 = 0…31
TR1 = 0…19
0=Clear All Parameters
1= Clear the 1st Min/Max Record
2= Clear the 2nd Min/Max Record
35=Clear the 35th Min/Max Record
4 40609-10 Status 1 Count x
M Register Set
Value
00
9,999,999
•••Status 1 Count Register Start Value x
1,000,000
5 40611-12 Status 1 Count
X 1 Register Set
Value
00
999,999
•••Status 1 Count Register Start Value x 1
6 40613-14 Status 2 Count x
M Register Set
Value
00
9,999,999
•••Status 2 Count Register Start Value x
1,000,000
7 40615-16 Status 2 Count
X 1 Register Set
Value
00
999,999
•••Status 2 Count Register Start Value x 1
8 40617-18 GWh Fwd
Register Set
Value
00
9,999,999
•••Sets the GWh Fwd Register to the
desired Value
9 40619-20 kWh Fwd
Register Set
Value
00
999,999
•••Sets the kWh Fwd Register to the
desired Value
10 40621-22 GWh Rev
Register Set
Value
00
9,999,999
•••Sets the GWh Rev Register to the
desired Value
11 40623-24 kWh Rev
Register Set
Value
00
999,999
Sets the kWh Rev Register to the
desired Value
12 40625-26 GVARh Fwd
Register Set
Value
00
9,999,999
••Sets the GVARh Fwd Register to the
desired Value
13 40627-28 kVARh Fwd
Register Set
Value
00
999,999
••Sets the kVARh Fwd Register to the
desired Value
14 40629-30 GVARh Rev
Register Set
Value
00
9,999,999
••
Sets the GVARh Rev Register to the
desired Value
Command Table
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description