User Manual
64 Publication 1408-UM001B-EN-P - May 2008
Appendix A Powermonitor 1000 Data Tables
Log Request Table Parameters
CSP File No. N17
CIP Instance 10
No. of Elements 11
No. of Words 11
Data Type Integer
Data Access Read/Write
Log Request Table
Element
No.
Modbus
Address
Element Name Default
Value
Range
TR1
TR2
EM1
EM2
EM3
Description
0 40701 Selected Log 0 0…5 •••••Selects the log that information is
returned from. Once a single request
has been made the auto return feature
will bring back successive records
each time the log is read. Some logs
support individual record requests.
1 = Unit Status Log
2 = Min/Max Log
3 = Energy Log
4 = Load Factor Log
5 = Time of Use Log kWh
6 = Time of Use Log kVAR
7 = Time of Use Log kVA
If your catalog number does not
support the requested log item the
power monitor will ignore the request.
1 40702 Chronology of
Auto Return
Data
10…1•••••The date chronology of the returned
records.
0 = Reverse direction
1 = Forward direction
2 40703 The Min/Max
record to be
returned
00…35
0…31
0…15
•• •Selects the Min/Max record number
to be returned. See the table for
Min/Max record list.
0 = Use incremental return and the
chronology selected.
EM3 = 1…35
TR2 = 1…31
TR1 = 1…15
3 40704 Number of Unit
Status Records
-1…50•••••On a read of this table the value of this
parameter is the number of Unit
Status Records available. This log is
only returned using the incremental
return method.