User Manual
Publication 1408-UM001B-EN-P - May 2008 67
Powermonitor 1000 Data Tables Appendix A
Discrete Results Parameters
CSP File No. N19
CIP Instance 12
Applies to All models
No. of Elements 6
No. of Words 6
Data Type Integer
Data Access Read
Discrete Results
Element
No.
Modbus
Address
Element Name Range Description
0 30001 Status Input States 0…3 Indicates the current states of the status input.
Bit 0 = Status 1 activated
Bit 1 = Status 2 activated
Bit 2…15 = Reserved
1 30002 Output Word 0…15 Bit 0 = KYZ relay actuated
Bit 1 = KYZ output forced on
Bit 2 = KYZ output forced off
Bit 3 = External demand pulse timeout
Bit 4 = Terminal Locked
Bit 5…15 = Reserved
2 30003 Reserved 0 Reserved for future use.
3 30004 Reserved 0 Reserved for future use.
4 30005 Reserved 0 Reserved for future use.
5 30006 Reserved 0 Reserved for future use.