User Manual
68 Publication 1408-UM001B-EN-P - May 2008
Appendix A Powermonitor 1000 Data Tables
Wiring Diagnostics Results Parameters
CSP File No. F20
CIP Instance 13
No. of Elements 21
No. of Words 42
Data Type Float
Data Access Read
Wiring Diagnostics Results
Element
No.
Modbus
Address
Element Name Units Range
TR1
TR2
EM1
EM2
EM3
Description
0 30101-2 Wiring Status 0…5 •••••This is the overall status of the
wiring diagnostic test.
0 = Pass
1 = Failed
2 = Input Level Low
3 = Disabled
4 = Waiting Command
5 = Out of range
1 30103-4 Voltage Input
Missing
-1…123 •••••Reports on all three phases.
-1 = Test not run.
0 = Test passed.
1 = Phase 1 missing
2 = Phase 2 missing
3 = Phase 3 missing
12 = Phase 1 and 2 missing
13 = Phase 1 and 3 missing
23 = Phase 2 and 3 missing
123 = All phases missing
2 30105-6 Voltage Input
Inverted
-1…123 •••••Reports on all three phases.
-1 = Test not run.
0 = Test passed.
1 = Phase 1 inverted
2 = Phase 2 inverted
3 = Phase 3 inverted
12 = Phase 1 and 2 inverted
13 = Phase 1 and 3 inverted
23 = Phase 2 and 3 inverted
123 = All phases inverted