6 30213-14 L3-N Volts 0.000…9,999,999 •• Phase 3 scaled RMS Voltage
7 30215-16 Average L-N Volts 0.000…9,999,999 •• Averaged RMS Voltage
8 30217-18 L1-L2 Volts 0.000…9,999,999 •• Line 1 to Line 2 Volts
9 30219-20 L2-L3 Volts 0.000…9,999,999 •• Line 2 to Line 3 Volts
10 30221-22 L3-L1 Volts 0.000…9,999,999 •• Line 3 to Line 1 Volts
11 30223-24 Average L-L Volts 0.000…9,999,999 •• Average Line to Line Volts
12 30225-26 Frequency 40.0 Hz…70.0 Hz •• Last frequency reading.
13 30227-28 Percent Current
Unbalance
0.0…100.0 •• Percent maximum deviation from
Ave. / Ave.
14 30229-30 Percent Voltage
Unbalance
0.0…100.0 •• Percent Maximum deviation from
Ave. / Ave.
15 30231-32 Metering Iteration 0…9,999,999 •• Increments by 1 for each new
metering calculation.
Volts, Amps, Frequency Results
Element
No.
Modbus
Address
Element Name Range
TR1
TR2
EM1
EM2
EM3
Description
Power Results Parameters
CSP File No. F22
CIP Instance 15
No. of Elements 17
No. of Words 34
Data Type Float
Data Access Read
Power Results
Element
No.
Modbus
Address
Element Name Range
TR1
TR2
EM1
EM2
EM3
Description
0 30301-2 L1 True Power
Factor
-100.0…+100.0 ••Percent ratio between power and
apparent power. The value is
signed to (+) leading and (-)
lagging.
1 30303-4 L2 True Power
Factor
-100.0…+100.0 ••
2 30305-6 L3 True Power
Factor
-100.0…+100.0 ••
3 30307-8 3 Phase True
Power Factor
-100.0…+100.0 ••
4 30309-10 L1 kWatts +/- 0.000…9,999,999 ••Line 1 kWatts
5 30311-12 L2 kWatts +/- 0.000…9,999,999 ••Line 2 kWatts