User Manual

Publication 1408-UM001B-EN-P - May 2008 73
Powermonitor 1000 Data Tables Appendix A
4 30409-10 GWh Fwd 0…9,999,999 •••Forward gigawatt hours
5 30411-12 kWatth Fwd 0.000…999,999 •••Forward kilowatt hours
6 30413-14 GWh Rev. 0…9,999,999 •••Reverse gigawatt hours
7 30415-16 kWatth Rev. 0.000…999.999 •••Reverse kilowatt hours
8 30417-18 GWh Net +/- 0…9,999,999 •••Net gigawatt hours
9 30419-20 kWatth Net +/- 0.000…999,999 •••Net kilowatt hours
10 30421-22 GVARH Fwd 0…9,999,999 ••Forward gigaVAR hours
11 30423-24 kVARh Fwd 0.000…999,999 ••Forward kiloVAR hours
12 30425-26 GVARH Rev. 0…9,999,999 ••Reverse gigaVAR hours
13 30427-28 kVARh Rev. 0.000…999,999 ••Reverse kiloVAR hours
14 30429-30 GVARH Net +/- 0…9,999,999 ••Net gigaVAR hours
15 30431-32 kVARh Net +/- 0.000…999,999 ••Net kiloVAR hours
16 30433-34 GVAh Net 0…9,999,999 ••Net gigaVA hours
17 30435-36 kVAh 0.000…999,999 ••Net kiloVA hours
18 30437-38 Metering Iteration 0…9,999,999 •••Increments by 1 for each new
metering calculation.
Energy Results
Element
No.
Modbus
Address
Element Name Range
TR1
TR2
EM1
EM2
EM3
Description
Demand Results Parameters
CSP File No. F24
CIP Instance 17
No. of Elements 9
No. of Words 18
Data Type Float
Data Access Read
Demand Results
Element
No.
Modbus
Address
Element Name Range
TR1
TR2
EM1
EM2
EM3
Description
0 30501-2 kWatt Demand +/- 0.000…9,999,999 ••The average real power during the
last demand period.
1 30503-4 kVAR Demand +/- 0.000…9,999,999 ••The average reactive power during
the last demand period.
2 30505-6 kVA Demand 0.000…9,999,999 ••The average apparent power during
the last demand period.