User Manual

74 Publication 1408-UM001B-EN-P - May 2008
Appendix A Powermonitor 1000 Data Tables
3 30507-8 Demand PF -100.0…+100.0 ••The average demand for PF during
the last demand period.
4 30509-10 Projected kWatt
Demand
+/- 0.000…9,999,999 ••The projected total real power for
the current period.
5 30511-12 Projected kVAR
Demand
+/- 0.000…9,999,999 ••The projected total reactive power
for the current period.
6 30513-14 Projected kVA
Demand
0.000…9,999,999 ••The projected total apparent power
for the current period.
7 30515-16 Elapsed Demand
Period Time
0.00…99.99 ••The amount of time that has
elapsed during the current period.
8 30517-18 Metering Iteration 0…9,999,999 ••Increments by 1 for each new
metering calculation.
Demand Results
Element
No.
Modbus
Address
Element Name Range
TR1
TR2
EM1
EM2
EM3
Description
Unit Status Log Results Parameters
CSP File No. N25
CIP Instance 18
Applies to All models
No. of Elements 13
No. of Words 13
Data Type Integer
Data Access Read
Unit Status Log Results
Element
No.
Modbus
Address
Element Name Range Description
0 30601 Status Record Internal
Identifier
1…50 Used to verify record sequence when returning multiple
records.
1 30602 Timestamp Year of record - The year when the record was recorded.
2 30603 Timestamp Month/Day - The month and day when the record was recorded.
3 30604 Timestamp Hour/Minute - The hour and minute when the record was recorded.
4 30605 Timestamp
Seconds/Hundredths
- The seconds and hundredths when the record was recorded.
5 30606 Status Event Type 0…512 Indicates the type of status event that has occurred.
6 30607 General Code 0…4096 Indicates general information about the status event.
7 30608 Information Code 0…256 Indicates specific information about the status event.