User Manual
76 Publication 1408-UM001B-EN-P - May 2008
Appendix A Powermonitor 1000 Data Tables
Unit Status Log Codes
Status Event Type
(Decimal)
Event # General Code (Decimal) Code # Information Code (Decimal) Code #
Self Test Status 1 Pass 0
Flash Memory 1 Overall Status 1
Boot Code Checksum 2
Application Code Checksum 4
Calibration Data CRC 8
No Calibration Data 16
Wrong Application FRN 32
Invalid Model Type 64
WIN Mismatch 128
Missing Upgrade Block 256
SRAM 2 Failed Read/Write Test 1
NVRAM 4 Failed Read/Write Test 1
SPI Interface 8 SPI Device Not Responding 1
SPI Interface Failed 2
Real Time Clock 16 Real Time Clock Failed 1
Real Time Clock not Set 2
Watchdog Timer 32 Watchdog Time Out 1
Metering 64 Metering Status Failed 1
LCD Interface 128 LCD Interface Failure 1
Serial Communications 256 Serial Communication Port Failed 1
Ethernet Communications 512 Ethernet Communications Port Failed 1
Modbus Stack Initialization Failed 2
Demand Broadcast Thread Init Failed 4
SNTP Thread Init Failed 8
Input Over Range 1024 Input Over Range Voltage 1
Input Over Range Current 2
Voltage Phase Loss 2048 Voltage Channel 1 Loss 1
Voltage Channel 2 Loss 2
Voltage Channel 3 Loss 4
Process Error 4096