User Manual
82 Publication 1408-UM001B-EN-P - May 2008
Appendix A Powermonitor 1000 Data Tables
18 30919 Ethernet Communications 0…511 0 indicates normal operation.
Bit 0 = Ethernet Communications status
Bit 1 = SNTP Server timeout status
Bit 2 = Duplicate IP Address status
Bit 3 = Invalid IP/Netmask address
Bit 4 = Invalid gateway address
Bit 5 = Invalid SNTP time server address
Bit 6 = Modbus stack run status
Bit 7 = Demand broadcast thread run status
Bit 8 = SNTP thread run status
19 30920 Input Over Range 0…3 0 indicates normal operation.
Bit 0 = Voltage Input over range
Bit 1 = Current Input over range
20 30921 Phase Loss Detection 0…7 0 Indicates normal running condition.
Bit 0 = Loss of phase A
Bit 1 = Loss of phase B
Bit 2 = Loss of phase C
21 30922 Configuration Locked 0…1 Reports 1 if configuration lock is applied.
22 30923 Password Accepted 0…1 1 indicates the password is verified and active
23 30924 Error Recorded 0 Is incremented by 1 when an internal error
happens
24 30925 Troubleshooting Times
Remaining
0…30 Remaining times for troubleshooting mode.
Unit Run Status Results
Element
No.
Modbus
Address
Element Name Range Description