User Manual
Publication 1408-UM001B-EN-P - May 2008 85
Powermonitor 1000 Data Tables Appendix A
33 kVAR Demand •
34 kVA Demand •
35 PF Demand •
Load Factor Log Results Parameters
CSP File No. F30
CIP Instance 23
No. of Elements 14
No. of Words 28
Data Type Float
Data Access Read
Min/Max Parameter List
No. Parameter TR1 TR2 EM3
Load Factor Log Results
Element
No.
Modbus
Address
Element Name Range
TR1
TR2
EM1
EM2
EM3
Description
0 31101-2 Record Number 1…13 ••The record number of this data.
1 31103-4 End Date
yy/mm/dd
- ••The date that this record was stored.
2 31105-6 Elapsed Time 0.000…
9,999,999
••Amount of time (in hours) that has
elapsed since the last clear of the peak
and average values. Updated at the end
of each demand interval.
3 31107-8 Peak Demand
kWatts
+/-
0.000…9,999,
999
••The largest magnitude demand for
kwatts that occurred over all of the
demand intervals since the last clear
command or auto-clear day.
4 31109-10 Average Demand
kWatts
+/-
0.000…9,999,
999
••A running average of demand for
kwatts from the end of each demand
period since the last clear command or
auto-clear day.
5 31111-12 Load Factor
kWatts
0…100% ••Average Demand kW / Peak Demand
kW. This is a demand management
metric that indicates how ‘spiky’ (or
‘level’) a load is over a period of time
(usually 1 month). A value approaching
100% indicates a constant load.