User Manual

DIR 1000587R0002 (L3821)
(23)
3.3.4 Default settings
TheLSIG-MMaresuppliedbyABwiththefollowingpredenedparameters(SetAandSetB):
# Protection On/Off Thresholds Time Curve T.M. Trip
1 L — 1In 144s I
2
t Off —
2 S Off 6In 50ms K — —
3 I On 4In — — — —
4 G Off 0.2In 0.4s K — On
5 U Off 50% 5s Off
6 OT — Off
7 Language — Engl
8 Mains frequency
(1)
9 Sel. Neutral
(2)
10 S startup Off 6In 100ms
11 G startup Off 1In 100ms
12 Password — 0001
13 Measurement interval — 60min
14 Iw Off 3In 
15 MM On 2.5In — — —
Note:
(1)
=50HzforautomaticCircuit-BreakersIEC
60HzforautomaticCircuit-BreakersUL
(2)
=offfor3-poleversion
50%for4-poleversion