3.4.6 Information Menu
TheInformationMenuenablesviewingdatarelatingtoprotectionunitandtypeofcircuitbreaker.
1/2
Protection Unit
Circuit Breaker
Protection Unit
About
Enter
ESC+
+Enter
1/3
Protection Unit
Nr.:
Version
Normative
Software
G0000A03A
:LSIG-MM
:UL
:2,00
Device
:LSIG-MM
1/3
Circuit Breaker
Device
Nr.:
Rated Curr.
Installation
Maintenance
: 140G-N/4p
:1200 A
:Jan 12, 2013
:Jan 12, 2013
3.4.6.1 Information on trip and opening data
TheLSIG-MMunitssaveallinformationrelatingtotypeofprotectiontripped,openingdata,dateandtime.Usingthe“iTest”key,therelease
willshowallthesedatadirectlyonthedisplay.Thereisnoneedforanauxiliarypowersupplyforthisfunction.Withanauxiliarypowersupply,
informationisshownimmediatelyonthedisplaywithoutneedingtopressthe“iTest”key,andremainsdisplayeduntilthekeyispressed.
Informationisavailablefor48hourswiththerelaydisconnected.Thedatarelatingtothelast20tripsarestoredintheunit’smemory.Byconnec-
tingabatteryunitoryoucanretrieveallinformationrelatingtothelast20tripsrecorded.AccesstoviewtheopeningdataisviatheHistoricals
submenuintheMeasurementsmenu.Thefollowingisanexampleoftheinformationprovided:
AgainintheMeasurementsmenu,youcanviewthepercentageofcontactwear,whichisanindicationoftheelectricallifeofthecontactsinthe
circuitbreaker.
However,relayfunctionalityisinnowaymodiedbythepresenceofwearmessages.
Aprealarmmessage(wear>80%,“warning”LEDlightingup)indicatesthatwearhasreachedahighvalue.Analarmmessage(100%wear,
“alarm”LEDlightingup)indicatesthatthestateofcontactwearmustbechecked.
Thepercentageofweardependsontypeofcircuit-breakerandnumberofopeningsperformedbycircuit-breakerandbyabsolutecurrentinter-
ruptedduringeachopening.
3.5 DenitionofalarmsandsignalsfortheLSIG-MMunits
3.5.1 Optical signals
Signalling Description
Warning
(yellowpermanent)
•Theprealarmthresholdhasbeenexceeded;oneormorephaseswithcurrentvaluesintherange0.9xI
1
< I
LED <1.05xI
1
(ontheNe,itdependsonselectionmade;e.g.at50%,valuesarehalved);
•Presence,betweentwoorthreephases,ofunbalanceabovethevalueprogrammedfor“U”protection,
withprotectiontripdisabled;
 •Presenceofdistortedwaveformwithformfactor>2.1;
•Contactweargreaterthan80%(andlessthan100%);
•WARNINGThresholdI
w
exceeded;
•Circuit-breakerstateerror;
•Congurationerror;
•Settingsinconsistency.
Warning LED
(yellow0.5Hz)
•WARNINGthresholdfortemperatureinsiderelayisexceeded.
Warning LED
(yellow2Hz)
 •ALARMthresholdfortemperatureinsiderelayisexceeded.
•PresenceofoneormoreoverloadedphaseswithcurrentvaluesI>1.3I1(protection“L”timing)
(ontheNe,itdependsonselectionmade;e.g.at200%,valuesaredoubled)*;
•TiminginprogressforprotectionfunctionS;
•TiminginprogressforprotectionfunctionG;
Alarm LED(red) •Timingwhenunbalancebetweenphases(protectionU)exceedsthevaluesetinthecongurationwith
protectiontripsettoon;
•Contactwear=100%;
•RatingPlugdisconnected;
•TripCoil(TC)disconnected;
•Keyplugerror;
•Currentsensorsdisconnected;
•Installationerror.
*IEC60947-2StandarddenestimingthresholdLforcurrent:1.05<I<1.3I1
n. 02
LProtection
I1: 625 AI3: 623 A
I2: 617 A Ne: > 10.0kA
Jan 06, 2013 08:52:11:733
Last Trip
NumberofopeningsduetoprotectionsandTRIPtests
Indicationforprotectiontripped
Valueofthecurrentsinterruptedonphases(L1,L2,L3),neutral(Ne)andGround(ifGhasbeentripped).