Rockwell Automation Publication 1426-UM001F-EN-P - November 2013 233
PowerMonitor 5000 Unit Data Tables Appendix A
Configuration.Instance
Table 43 - Table Properties
CIP 102
No. of Elements 43
Length in Words 80
Data Type Varies
Data Access Read/Write
Table 44 - Configuration.Instance Data Table
Start
Byte
Size Type Tag Name Description Units Range
0 1 SINT MeterMode Configures the input wiring for metering.
0 = Demo
1 = Split Phase
2 = Wye
3 = Delta 2 CT
4 = Delta 3 CT
5 = Open Delta 2 CT
6 = Open Delta 3 CT
7 = Delta Gnd B Ph 2 CT
8 = Delta Gnd B Ph 3 CT
9 = Delta High Leg
Mode 0…9
1 SINT Pad01 For alignment purpose
INT Pad02 For alignment purpose
4 4 Real VLinePTPrimary The primary voltage value of the PT transformer V 0…1,000,000
8 4 Real VLinePTSecondary The secondary voltage value of the PT transformer V 0…690
12 4 Real ILineCTPrimary The primary ampere value of the CT transformer A 0…1,000,000
16 1 SINT ILineCTSecondary The secondary ampere value of the CT transformer A 5
1SINT Pad03
2 INT Pad04 For alignment purpose
20 4 Real VNPTPrimary The primary voltage value of the PT transformer V 0…1,000,000
24 4 Real VNPTSecondary The secondary voltage value of the PT transformer V 0…690
28 4 Real I4CTPrimary The primary ampere value of the CT transformer A 0…1,000,000
32 1 SINT I4CTSecondary The secondary ampere value of the CT transformer A 5
1 SINT Pad05 For alignment purpose
2 INT Pad06 For alignment purpose
36 4 Real NominalVToVVoltage Nominal voltage value or voltage rating of the system being metered. V 0…1,000,000
40 4 DINT Pad07 For alignment purpose N/A 0…0
44 4 Real NominalFreq Nominal frequency of the system.
50=50 Hertz
60=60 Hertz
Hertz 50 or 60