234 Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A PowerMonitor 5000 Unit Data Tables
48 1 SINT RealTimeUpdateRate Selects the update rate for the realtime table and the setpoint
calculations.
0 = Single cycle averaged over 8 cycles
1 = Single cycle averaged over 4 cycles
2 = 1 cycle with no averaging
3 = 200 ms per EN61000-4-30 (M6 and M8 Only)
Meter
Averaging
0…3
1 SINT Pad08 For alignment purpose
2 INT Pad09 For alignment purpose
52 2 INT DeviceFaultAction This parameter determines the action when a unit error occurs.
0 = Halt on error and make status indicator solid red
1 = Reset power monitor hardware
Error Action 0…1
54 2 INT EnergyLogInverval Selects how often a record is logged (minutes). A value of 0 disables
periodic logging of records. A value of -1 causes the logging of records
to be synchronized to the end of the demand Interval.
Energy Interval
(Minutes)
-1…60
56 2 INT EnergyLogMode This parameter sets the action of the log once it has filled to capacity.
0 = Fill and Stop
1 = Overwrite oldest record.
Energy Log
Mode
0…1
58 2 INT TOU AutoStoreDay Automatically stores the current record for the month replacing an
older record if the log is full. The log holds 12 records plus the current
record.
0 = Disable storing records
1 = Store and clear on the first day of the month
2 = 2nd of month
3 = 3rd day of month
…
31 = 31st day of month
If set to 29…31 the last day of every month stores a record.
AutoStore 0…31
60 1 SINT DemandSource When item ‘Demand Broadcast Master Select’ of the Ethernet table is
set to a master selection of 0…2 sets the type of master input. In this
case item ‘3’ is ignored. When the ‘Demand Broadcast Master Select’
of the Ethernet table is set to slave, then any of these inputs can set
the end of the demand period.
0 = Internal Timer
1 = Status Input 2
2 = Controller Command
3 = Ethernet Demand Broadcast
Demand Period
Length
0…3
1 SINT Pad10 For alignment purpose
2 INT Pad11 For alignment purpose
64 1 SINT DemandPeriodLength Specifies the desired period for demand calculations. When set to 0
there is no projected demand calculations. If the internal timer is
selected a setting of 0 turns the demand function off.
Number
Demand
Periods
0…99
1 SINT Pad12 For alignment purpose
2 INT Pad13 For alignment purpose
68 1 SINT NumberOfDemandCycles Specifies the number of demand periods to average for demand
measurement.
Demand Sync
Delay
1…15
1 SINT Pad14 For alignment purpose
2 INT Pad15 For alignment purpose
Table 44 - Configuration.Instance Data Table
Start
Byte
Size Type Tag Name Description Units Range