72 2 INT ForcedDemandSyncDelay When the power monitor is configured for external demand control
the unit delays for xxx seconds after the expected control pulse has
not been received. The demand period starts over and a record is
recorded in the status log
0 = Wait forever
1…900 = Wait this many seconds before starting a new demand
period.
IMPORTANT: This setting becomes active when an external input is
used to end the demand period.
Demand
Broadcast
Mode
0…900
2 INT Pad16 For alignment purpose
76 1 SINT DemandBroadcastMode Demand Ethernet broadcast selection.
0 = Slave
1 = Master
IMPORTANT: There can be only one master per demand network.
Demand
Broadcast
Mode
0…1
1 SINT Pad17 For alignment purpose
78 2 INT DemandBroadcastPort The common port for demand broadcast messages. Demand
Broadcast Port
300…400
80 1 SINT KYZOutputMode The parameter selected pulses the KYZ output at a rate that equals the
parameter value divided by KYZ scale.
0 = Setpoint Control
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah
KYZ Output
Parameter
0…6
1 SINT Pad18 For alignment purpose
2 INT Pad19 For alignment purpose
84 4 DINT KYZPulseScale The KYZ output parameter divided by the scale is the output pulse
rate. Example: Wh is selected for the parameter and 1,000 is the
scale value. The output is pulsed every kWh.
KYZ Output
Scale
1…100,000
88 2 INT KYZPulseDuration Set as 50…1000 to indicate the duration of the pulse in milliseconds,
or set to 0 for KYZ-style transition output. (Toggle)
IMPORTANT: The value for delay is rounded off to the nearest 10 ms
internally during this function.
KYZ Output
Duration
0 or 50…1000
2 INT Pad20 For alignment purpose
92 1 SINT R1OutputMode The parameter selected will pulse the relay 1 output at a rate that
equals the parameter value divided by relay 1 scale.
0 = Setpoint Control
1 = Wh Fwd
2 = Wh Rev
3 = VARh Fwd
4 = VARh Rev
5 = VAh
6 = Ah
Relay 1 Output
Parameter
0…6
1 SINT Pad21 For alignment purpose
2 INT Pad22 For alignment purpose
96 4 DINT R1PulseScale The relay 1 output parameter divided by the relay 1 scale is the output
pulse rate. Example: Wh is selected for the parameter and 1,000 is the
scale value. The output is pulsed every kWh.
Relay 1 Output
Scale
1…100,000