Rockwell Automation Publication 1426-UM001F-EN-P - November 2013 259
PowerMonitor 5000 Unit Data Tables Appendix A
32 Real Parameter
Selection 10
Selection of the input parameter from the Setpoint Parameter Selection List.00…105
33 Real Input Reference
Selection 10
Selects the type of input conditioning for non boolean parameters.
0 = Absolute Value
00
34 Real Test Condition 10 0 = Disabled
1 = Less Than
2 = Greater Than
3 = Equals
0 0…3
35 Real Evaluation Type
10
0 = Magnitude
1 = State
2 = Percent of Reference (not supported in the M5 model)
3 = Percent of Sliding Reference (not supported in the M5 model)
00…3
36 Real Threshold 10 The value, percent, or state that triggers the output action. 0 -10,000,000…
10,000,000
37 Real Hysteresis 10 The value in magnitude or percent of reference at which the output action is deasserted.
Example: A less than condition deasserts at (threshold + hysteresis), a greater than condition
deasserts at (threshold - hysteresis).
0 0…10,000,000
38 Real Assert Delay
Seconds 10
The amount of time to delay the output action after a setpoint trigger occurs. Minimum equals
realtime update rate setting.
0 0.000…3600
39 Real Deassert Delay
Seconds 10
The amount of time to delay deassertion after the setpoint trigger releases. Minimum equals
realtime update rate setting.
0 0.000…3600
40…49 Real Reserved Future Use 0 0
Table 64 - Configuration.Setpoints_6_10 Data Table
Element
Number
Type Tag Name Description Default Range