PowerMonitor 5000 Unit Data Tables Appendix A
2 Int16 Logic_Level_1_Gates_Active (M6) Actuation Status of Level 1 Gates 0 … 65535
Bit 0 Level1_Gate1_Output 1 Indicates gate logic output is true 0 or 1
Bit 1 Level1_Gate2_Output 1 Indicates gate logic output is true 0 or 1
Bit 2 Level1_Gate3_Output 1 Indicates gate logic output is true 0 or 1
Bit 3 Level1_Gate4_Output 1 Indicates gate logic output is true 0 or 1
Bit 4 Level1_Gate5_Output 1 Indicates gate logic output is true 0 or 1
Bit 5 Level1_Gate6_Output 1 Indicates gate logic output is true 0 or 1
Bit 6 Level1_Gate7_Output 1 Indicates gate logic output is true 0 or 1
Bit 7 Level1_Gate8_Output 1 Indicates gate logic output is true 0 or 1
Bit 8 Level1_Gate9_Output 1 Indicates gate logic output is true 0 or 1
Bit 9 Level1_Gate10_Output 1 Indicates gate logic output is true 0 or 1
Bit 10 … 15 Reserved Future Use 0
3 Int16 Metering_Status Metering Conditions Status 0…65,535
Bit 0 Virtual_Wiring_Correction 1 = Virtual Wiring Correction ON 0…1
Bit 1 Voltage_Phase_V1 1 = Loss of V1 metering voltage 0…1
Bit 2 Voltage_Phase_V2 1 = Loss of V2 metering voltage 0…1
Bit 3 Voltage_Phase_V3 1 = Loss of V3 metering voltage 0…1
Bit 4 Voltage_Over_Range_Indication 1 = A Voltage over range status condition exists 0…1
Bit 5 Ampere_Over_Range_Indication 1 = An Amperage over range status condition exists 0…1
Bit 6 Wiring_Diagnostics_Active 1 = The wiring diagnostics is currently calculating wiring condition 0…1
Bit 7…15 Reserved Reserved for future use 0
4 Int16 Over_Range_Information Indicates which input is over range 0…65,535
Bit 0 V1G_Over_Range 1 = V1G input is over input range 0…1
Bit 1 V2G_Over_Range 1 = V2G input is over input range 0…1
Bit 2 V3G_Over_Range 1 = V3G input is over input range 0…1
Bit 3 VNG_Over_Range 1 = VNG input is over input range 0…1
Bit 4 I1_Over_Range 1 = I1 input is over input range 0…1
Bit 5 I2_Over_Range 1 = I2 input is over input range 0…1
Bit 6 I3_Over_Range 1 = I3 input is over input range 0…1
Bit 7 I4_Over_Range 1 = I4 input is over input range 0…1
Bit 8…15 Reserved Reserved for future use 0
5 Int16 PowerQuality_Status Power Quality Conditions Status 0…65,535
Bit 0 Sag_Indication_Detected 1 = A sag event was detected in the last metering cycle 0…1
Bit 1 Swell_Indication_Detected 1 = A Swell event was detected in the last metering cycle 0…1
Bit 2…15 Reserved Reserved for future use 0
Table 116 - Status.Alarms Data Table
Element
Number
Type Tag Name Description Range