304 Rockwell Automation Publication 1426-UM001F-EN-P - November 2013
Appendix A PowerMonitor 5000 Unit Data Tables
6 Int16 Logs_Status Logs Condition Status 0… 65,535
Bit 0 Data_Log_Full_Fill_And_Stop Is Set when fill and stop is configured and log is at least 80% filled 0…1
Bit 1 Event_Log_Full_Fill_And_Stop Is Set when fill and stop is configured and log is at least 80% filled 0…1
Bit 2 Setpoint_Log_Full_Fill_And_Stop Is Set when fill and stop is configured and log is at least 80% filled 0…1
Bit 3 PowerQuality_Log_Full_Fill_And_Stop Is Set when fill and stop is configured and log is at least 80% filled 0…1
Bit 4 Energy_Log_Full_Fill_And_Stop Is Set when fill and stop is configured and log is at least 80% filled 0…1
Bit 5 Waveform_Full Is Set when log is at least 80% filled 0…1
Bit 6 TriggerData_Full_Fill_And_Stop Is Set when fill and stop is configured and log is at least 80% filled 0…1
Bit 7…15 Reserved Reserved for future use 0
7 Int16 Output_Pulse_Overrun The output pulse rate exceeds the configured capability 0
Bit 0 KYZ_Pulse_Overrun The KYZ output pulse rate exceeds the configured capability
Bit 1 Relay1_Pulse_Overrun The Relay 1 output pulse rate exceeds the configured capability
Bit 2 Relay2_Pulse_Overrun The Relay 2 output pulse rate exceeds the configured capability
Bit 3 Relay3_Pulse_Overrun The Relay 3 output pulse rate exceeds the configured capability
Bit 4…15 Reserved Reserved for future use
8 Int16 IEEE1159_Over_Voltage Over Voltage Condition 0…65535
Bit 0 IEEE1159_Over_Voltage_V1 1 = An over voltage is detected on V1 0…1
Bit 1 IEEE1159_Over_Voltage_V2 1 = An over voltage is detected on V2 0…1
Bit 2 IEEE1159_Over_Voltage_V3 1 = An over voltage is detected on V3 0…1
Bit 3... 15 Reserved Reserved for future use 0
9 Int16 IEEE1159_Under_Voltage Under Voltage Condition 0…65535
Bit 0 IEEE1159_Under_Voltage_V1 1 = An under voltage is detected on V1 0…1
Bit 1 IEEE1159_Under_Voltage_V2 1 = An under voltage is detected on V2 0…1
Bit 2 IEEE1159_Under_Voltage_V3 1 = An under voltage is detected on V3 0…1
Bit 3... 15 Reserved Reserved for future use 0
10 Int16 IEEE1159_Imbalance_Condition IEEE1159 Imbalance 0…65535
Bit 0 IEEE1159_Imbalance_Condition_Volts 1 = An Imbalance is detected on Voltage 0…1
Bit 1 IEEE1159_Imbalance_Condition_Current 1 = An Imbalance is detected on Current 0…1
Bit 2...15 Reserved Reserved for future use 0
11 Int16 IEEE1159_DCOffset_Condition IEEE1159 DC Offset Condition 0…65535
Bit 0 IEEE1159_DCOffset_Condition_V1 1 = A DC offset exceed limitation is detected on V1 0…1
Bit 1 IEEE1159_DCOffset_Condition_V2 1 = A DC offset exceed limitation is detected on V2 0…1
Bit 2 IEEE1159_DCOffset_Condition_V3 1 = A DC offset exceed limitation is detected on V3 0…1
Bit 3... 15 Reserved Reserved for future use 0
12 Int16 IEEE1159_Voltage_THD_Condition IEEE1159 Voltage THD Condition 0…65535
Bit 0 IEEE1159_Voltage_THD_Condition_V1 1 = A THD exceed limitation is detected on V1 0…1
Bit 1 IEEE1159_Voltage_THD_Condition_V2 1 = A THD exceed limitation is detected on V2 0…1
Bit 2 IEEE1159_Voltage_THD_Condition_V3 1 = A THD exceed limitation is detected on V3 0…1
Bit 3... 15 Reserved Reserved for future use 0
Table 116 - Status.Alarms Data Table
Element
Number
Type Tag Name Description Range