Chapter 4 Troubleshoot the Module
Module Status Indicator
ControlNet A and ControlNet B Status Indicators Together
ControlNet A or ControlNet B Status Indicator Individually
State Probable Cause
Off No power applied to device
Alternating Red/Green LED power up test (module self-test)
Flashing Red Recoverable fault has occurred:
Firmware (NVS) download is currently in progress
The MAC ID has changed
CPU load has been exceeded
Solid Red Unrecoverable fault has occurred:
Self test failure (checksum failure at power up, RAM test
failure at power up
Firmware fatal error
Solid Green Device is operating correctly (normal mode)
State Probable Cause
Both Off Reset, no power or entire network interface deactivated
Alternating Red/Green Self test mode
Alternating Red/Off Bad/invalid node configuration (such as duplicate MAC ID)
Both Red Failed link interface or failed module
State Probable Cause
Off Channel is disabled or channel is not supported
Flashing Red/Green Invalid link configuration
Flashing Red/Off Severe Link error - link fault or no MAC frames received
Flashing Green/Off Temporary channel error or listen-only
Solid Green Normal operation - MAC frames are being received without
detected errors