Installing the XM-440 Master Relay Module 39
Network Status (NS) Indicator
Relay Indicators (4 in all)
Basic Operations
Powering Up the Module
The XM-440 performs a self-test at power-up. The self-test includes an LED
test and a device test. During the LED test, the indicators will be turned on
independently and in sequence for approximately 0.25 seconds.
The device test occurs after the LED test. The Module Status (MS) indicator is
used to indicate the status of the device self-test.
Color State Description
No color Off Module is not online.
• Module is autobauding.
• No power is applied to the module, look at Module
Status LED.
Green Flashing Module is online (DeviceNet) but no connections are
currently established.
Solid Module is online with connections currently
established.
Red Flashing One or more I/O connections are in the Timed-Out
state.
Solid Failed communications (Duplicate MAC ID or Bus-off).
Color State Description
Red Off On-board relay is not activated.
Solid On-board relay is activated.
Device Self-Test Status
MS Indicator State Description
Flashing Red and Green Device self test is in progress.
Solid Green or Flashing Green Device self test completed successfully, and the
firmware is valid and running.
Flashing Red Device self test completed, the hardware is OK, but the
firmware is invalid. Or, the firmware download is in
progress.
Solid Red Unrecoverable fault, hardware failure, or Boot Loader
program may be corrupted.