108 DeviceNet Objects
Instance Attributes
Services
1 Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
Table C.40 Transducer Object Instance Attributes
Attr ID
Access
Rule Name Data Type Description Semantics
3 Get DC Bias REAL The measured average DC
bias of the transducer
signal in volts.
Volts
4 Get Status BOOL Indicates whether a
transducer fault exists
(the measured DC Bias is
outside the range
specified by Fault High
and Low).
0 = No fault
1 = A transducer fault exists
7 Get/Set Fault High REAL The maximum expected
DC Bias voltage from the
transducer in volts.
Volts
8 Get/Set Fault Low REAL The minimum expected
DC Bias voltage from the
transducer in volts.
Volts
9 Get/Set Power Type USINT Indicates the type of
power supplied to the
transducer.
0 = No power supplied
3 = Bias current for passive
magnetic sensors
13 Get/Set DC Bias Time
Constant
REAL The time constant value
used for exponential
averaging of the DC Bias
value (a low pass
filter/output smoothing
filter).
Seconds
Table C.41 Transducer Object Services
Service
Code Class/Instance Usage Name Description
0E
h
Instance Get_Attribute_Single Returns a single attribute.
10
h
Instance Set_Attribute_Single
Sets a single attribute.
1