Owner manual

Publication GMSI10-UM004B-EN-P - May 2010
DeviceNet Objects 109
4-20mA Output Object
(Class ID 32A
H
)
The 4-20mA Output Object models the configuration of a 4-20mA output
signal.
Class Attributes
The 4-20mA Output Object provides no class attributes.
Instances
There are 2 instances of this object.
Instance Attributes
Table C.42 4-20mA Output Object Instance Attributes
Attr ID
Access
Rule Name Data Type Description Semantics
3 Get Value REAL The current output value. mA
4 Get/Set Enable BOOL Indicates whether this
4-20mA output is
enabled.
0 = Disabled
1 = Enabled
5 Get/Set Max Range REAL The measured value
associated with 20mA.
6 Get/Set Min Range REAL The measured value
associated with 4mA.
7 Get/Set Measurement
Identifier Path
EPATH Identifies the class,
instance, and attribute of
a measurement value that
this 4-20mA output is
tracking.
See Parameter Object instances
2 and 3.
See DeviceNet Specification
Volume 1 Appendix I.