Publication GMSI10-UM013D-EN-P - May 2010
DeviceNet Objects 137
Instance Attributes
Services
1 Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
6 gSE Overall Measurement 2 gSE Overall measurement for Channel 2
7 Sum Harmonics
Measurement 1
Sum Harmonics measurement for Channel 1
8 Sum Harmonics
Measurement 2
Sum Harmonics measurement for Channel 2
Table C.26 Analog Input Point Object Instances
Instance Name Description
Table C.27 Analog Input Point Object Class Attributes
Attr ID
Access
Rule Name Data Type Description Semantics
3 Get Value REAL
4 Get Status BOOL Indicates if a fault or
alarm has occurred.
0 = Operating without alarms or
faults
1 = Alarm or fault condition
exists. The Value attribute may
not represent the actual field
value.
8 Get Value Data Type USINT Determines the data type
of the Value.
1 = REAL
147 Get Data Units ENGUNIT The units context of the
Value attribute.
See DeviceNet Specification
Volume 1 Appendix K.
Table C.28 Analog Input Point Object Services
Service
Code Class/Instance Usage Name Description
0E
h
Class/Instance Get_Attribute_Single Returns the contents of the
specified attribute.
10
h
Instance Set_Attribute_Single Sets the contents of the
specified attribute.
1