146 DeviceNet Objects
1 The Poll Connection Produced Connection Path and Size parameters cannot be set while the Poll connection is
already established with a master/scanner. Attempting to do so will result in an "Object State Conflict" error
(error code 0xC) These Parameter instances are a little more flexible than the actual Connection Object
attributes because they can be set while the connection is in the NON-EXISTENT state (before the
master/scanner allocates the connection).
Instance Attributes
44 No Channel 1 Band 4 Spectrum
Option
USINT 0 = Standard Spectrum
1 = gSE Spectrum
0
45 No Channel 2 Band 4 Spectrum
Option
USINT 0 = Standard Spectrum
1 = gSE Spectrum
0
46 No Poll Connection Produced
Connection Path
1
USINT 101-106, 199 (Assembly
Object instance number)
101
47 No Poll Connection Produced
Connection Size
1
UINT 4 - 124 124
Table C.30 Parameter Object Instances
Instance
Read
Only Name Data Type Valid Values Default Value
Table C.31 Parameter Object Instance Attributes
Attr ID
Access
Rule Name Data Type Description Semantics
1 Set Parameter
Value
Actual value of parameter See Table C.30 for a list of valid
values for each instance.
2 Get Link Path Size USINT Size of Link Path 0 (These Parameter instances do
not link directly to another
object attribute.)
3
Get
Link Path ARRAY of
DeviceNet
path
DeviceNet path to the
object for the Parameter
value.
Segment
Type/Port
BYTE See DeviceNet
Specification Volume 1
Appendix I for format.
Segment
Address
See DeviceNet
Specification Volume 1
Appendix I for format.