150 DeviceNet Objects
12 Get/Set Hysteresis REAL The amount on the safe
side of a threshold by
which the value must
recover to clear the alarm.
13 Get/Set Threshold (Setpoint
Multiplier)
REAL Indicates how the
thresholds should be
adjusted when the
setpoint multiplication
function is invoked.
0 = Disable alarm
> 0 = Multiply the thresholds by
the value
14 Get/Set Startup Period UINT The amount of time that
the Threshold (Setpoint)
Multiplier is applied after
the startup signal is
received.
Seconds
15 Get/Set Speed Range
Enable
BOOL Indicates whether this
alarm is enabled only
within a certain machine
speed range.
0 = No speed range (alarm is
always enabled)
1 = Speed range (alarm only
enabled within speed range)
16 Get/Set Speed Range High REAL Indicates the greater
threshold of the machine
speed range for which the
alarm is enabled (disabled
at greater speeds).
CPM
(must be greater than Speed
Range Low)
17 Get/Set Speed Range Low REAL Indicates the lesser
threshold of the machine
speed range for which the
alarm is enabled (disabled
at lesser speeds).
CPM
(Must be less than Speed
Range High)
18 Get/Set Name STRING2 A name to help identify
this alarm.
19 Get/Set Measurement
Identifier
EPATH Identifies the
measurement object to
which this alarm is
applied.
See Parameter Object instances
10 to 25.
20 Get/Set Inhibit Tach Fault BOOL Determines whether the
Tach Fault status is
prohibited during the
startup period.
0 = Tach Fault allowed
1 = Tach Fault inhibited
Table C.36 Alarm Object Instance Attributes
Attr ID
Access
Rule Name Data Type Description Semantics