Manual
Publication GMSI10-UM013D-EN-P - May 2010
DeviceNet Objects 157
Instance Attributes
Setting the Device Mode attribute to "1" (RUN) is equivalent to executing the
Start service. Setting the Device Mode attribute to "2" (PROGRAM) is
equivalent to executing the Stop service.
Services
Table C.45 Device Mode Object Instance Attributes
Attr ID
Access
Rule Name Data Type Description Semantics
3 Get/Set Device Mode UINT The operating mode of the
module.
0 = Power Up
1 = RUN
2 = PROGRAM
199 Set Backdoor
Service
USINT Setting this attribute is
equivalent to requesting
the specified service.
Set to one of the following
values to perform the specified
service:
0x05 = Reset
0x09 = Delete
0x15 = Restore
0x16 = Save
Table C.46 Device Mode Object Services
Service
Code Class/Instance Usage Name Description
0E
h
Instance Get_Attribute_Single Return the value of a single
attribute.
10
h
Instance Set_Attribute_Single Set the value of a single
attribute.
07
h
Instance Stop Transitions from Run to the
Program state.
06
h
Instance Start Validate the device
configuration settings and
transition to the Run state if
OK.
05
h
Instance Reset Transition to the Power Up
state. Load the non-volatile
configuration and transition
to the Run state if saved
configuration restored.