162 DeviceNet Objects
7 Get/Set Delay USINT The time period that the
voting logic must be true
before the relay is
activated.
0 to 25.5 seconds
(specified in tenths of seconds)
8 Get/Set Name STRING2 A name to help identify
the relay.
18 characters maximum
9 Get/Set Alarm Level BYTE Specifies what alarm
status values will cause
the relay to activate.
0 = Normal
1 = Alert
2 = Danger
3 = Disarm
4 = Xdcr Fault
5 = Module Fault
6 = Tachometer Fault
10 Get/Set Alarm Identifier
A
EPATH Identifies the first alarm
status the relay monitors.
See Parameter Object instances
26 to 30.
11 Get/Set Alarm Identifier
B
EPATH Identifies the second
alarm status the relay
monitors.
See Parameter Object instances
31 to 35.
12 Get/Set Logic USINT Indicates the number of
associated alarms that
must have a status value
specified by Alarm Level
in order to activate the
relay.
0 = Ignore Alarm Identifier B
and activate the relay based on
the status of Alarm Identifier
A.
1 = Activate the relay if the
status of either Alarm
Identifier A or B matches any
of the statuses specified by
Alarm Level.
2 = Activate the relay if the
status of both Alarm Identifier
A and B match any of the
statuses specified by Alarm
Level.
14 Get Relay Installed BOOL Indicates whether an
actual relay is associated
with this instance.
0 = Not installed
1 = Installed
Table C.50 Relay Object Instance Attributes
Attr ID
Access
Rule Name Data Type Description Semantics