Manual
Publication GMSI10-UM013D-EN-P - May 2010
DeviceNet Objects 175
Instances
There are 6 instances of this object.
Instance Attributes
Table C.64 Vector Measurement Object Instances
Instance Description
1 Channel 1 1X Vector Measurement
2 Channel 2 1X Vector Measurement
3 Channel 1 2X Vector Measurement
4 Channel 2 2X Vector Measurement
5 Channel 1 3X Vector Measurement
6 Channel 2 3X Vector Measurement
Table C.65 Vector Measurement Object Instance Attributes
Attr ID
Access
Rule Name Data Type Description Semantics
3 Get Magnitude
Value
REAL The measured magnitude
value.
4 Get Phase Value REAL The measured phase
value.
Degrees
Note: Note valid for instances 5
and 6.
5 Get Status BOOL Indicates if a fault or
alarm has occurred.
0 = Operating without alarms of
faults.
1 = Alarm or fault condition
exists. The Value attributes
may not represent the actual
field value.