Manual

Publication GMSI10-UM013D-EN-P - May 2010
180 Wiring Connections for Previous Module Revisions
WARNING
EXPLOSION HAZARD
Do not disconnect equipment unless power has been
removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless
power has been removed or the area is known to be
nonhazardous. Secure any external connections that mate
to this equipment by using screws, sliding latches, threaded
connectors, or other means provided with this product.
Terminal Block Assignments
No. Name Description
0 Xducer 1 (+) Vibration transducer 1 connection
1 Xducer 2 (+) Vibration transducer 2 connection
2 Buffer 1 (+) Vibration signal 1 buffered output
3 Buffer 2 (+) Vibration signal 2 buffered output
4 Tach/Signal In (+) Tachometer transducer/signal input, positive side
5 Xducer Vin Vibration transducer power input
6 Xducer V (+) Vibration transducer power supply output, positive side connect
to Xducer Vin for positive biased transducers or Xducer RTN for
negative biased transducers
7 TxD PC serial port, transmit data
8 RxD PC serial port, receive data
9
XRTN
1
Circuit return for TxD and RxD
10 Chassis Connection to DIN rail ground spring or panel mounting hole
11 4-20 mA 1 (+) 4-20 mA output
300 ohm maximum load
12 4-20 mA 1 (-)
13 Chassis Connection to DIN rail ground spring or panel mounting hole
14 Chassis Connection to DIN rail ground spring or panel mounting hole
15 Chassis Connection to DIN rail ground spring or panel mounting hole
16
Xducer 1 (-)
1
Vibration transducer 1 connection
17
Xducer 2 (-)
1
Vibration transducer 2 connection
18
Signal Common
1
Vibration buffered output return
19 TACH Buffer Tachometer transducer/signal output
20 Tachometer (-) Tachometer transducer/signal input, negative side and TACH
Buffer return
21 Xducer V (-) Vibration transducer power supply output, negative side connect
to Xducer RTN for positive biased transducer or Xducer Vin for
negative biased transducers and power
22 Xducer RTN Vibration transducer power return
23 CAN_High DeviceNet bus connection, high differential (white wire)