User Manual User Manual

9-2 Troubleshooting
The following flowchart is provided to aid in quick troubleshooting.
Figure 9.1 Troubleshooting Flowchart
See
Table 10.A
on page
10-3
See
Table 10.B
on page
10-4
See
Table 10.C
on page
10-4
See
Table 10.D
on page
10-4
See
Table 10.E
on page
10-5
YES
NO
Fault Displayed?
Define Nature
of Trouble
Motor will not start —
no output voltage to
motor
Motor rotates
but does not
accelerate to full
speed
Motor stops while
running
Miscellaneous
situations
See
Table 9.A
See
Table 9.C
See
Table 9.D
See
Table 9.E
See
Table 9.B
Table 9.A SMC Fault Display Explanation
Display Fault Code Possible Causes Possible Solutions
Line Loss
(with phase
indication)
1, 2, 3 Missing supply phase
Motor not connected properly
Check for open line (i.e., blown fuse)
Check for open load lead
Consult the factory
Shorted SCR 4, 5, & 6 Shorted Power Module Check for shorted SCR, replace power module if
necessary
Open Gate
(with phase
indication)
7, 8, & 9 Open gate circuitry
Loose gate lead
Perform resistance check; replace power module if
necessary
Check gate lead connections to the control module
PTC Power Pole
SCR Overtemp
10 & 11 Controller ventilation blocked
Controller duty cycle exceeded
Fan failure
Ambient temperature limit exceeded
Failed thermistor
Failed control module
Check for proper ventilation
Check application duty cycle
Replace fan
Wait for controller to cool or provide external cooling
Replace power module
Replace control module
Motor PTC 12 Motor ventilation blocked
Motor duty cycle exceeded
PTC open or shorted
Check for proper ventilation
Check application duty cycle
Wait for motor to cool or provide external cooling
Check resistance of PTC