Instruction Manual

4-2 Setup and Commissioning
1503-UM 053B-EN-P Ju ne 2013
An IntelliVAC unit shipped separately from the factory will have a
default configuration per Table 4.A.
Table 4.A DIP Switch Factory Default Settings
DIP switch SW1
DIP switch SW2
Description
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Altitude: 0 1000m
0
0
1
Drop-out time: 130 msec
0 1 1
Contactor config.: 400A EH
0
0
0
1
TDUV config.: No TDUV
0
Ext. cap TDUV time: 0.2 sec
0
0
Power-Up Safety: Enable
0
IntelliVAC units shipped in a complete MV controller (Bulletin
1500/1900) will be configured to suit the installed application (i.e.
contactor type). The user should verify the settings before energizing the
equipment. Table 4.B defines the settings for each switch.
Table 4.B IntelliVAC DIP Switch Explanation