User Manual
Publication 0160-5.18 - June 2003
B-22 DeviceNet Information
Class Code 0xB4 —
DN Interface Object
Instance 1 Attributes
➀ If set to a “9,” P9 - [Drive Status] (of the SSC Interface Profile) goes in the low byte of the assembly field, and P12 - [Input Status] (of the SSC Interface
Profile) goes in the high byte of the assembly field.
Common Services
Class Attributes: None Supported Number of Instances: 1
Attribute ID
Access
Rule
Name
Data
Type
Min/Max Default Description
1 Get Zero USINT 0 0 Returns zero.
2 Get Interface Select USINT 0 0 0 = Bulletin 160 SSC Interface.
3 Get
MAC ID
Switches
USINT 0 to 63 Reflects the state of the MAC ID switches.
4 Get Baud Switches USINT 0 to 3 Reflects the state of the Baud Rate switches.
5 Get/Set
Nonvolatile MAC
ID
USINT 0 to 63 63
Stored value of the MAC ID. This value is used when Baud
Rate Switches 7 and 8 are ON.
6 Get/Set Nonvolatile Baud USINT 0 to 2 0
Stored value of Baud Rate. This value is used when Baud
Rate Switches 7 and 8 are ON.
7
➀ Get/Set
Assembly
Word 0 Param
USINT 0 to 88 9
Bulletin 160 SSC Interface parameter number whose value is
used as the first word in Input Assembly 102.
8
➀ Get/Set
Assembly
Word 1 Param
USINT 0 to 88 0
Bulletin 160 SSC Interface parameter number whose value is
used as the second word in Input Assembly 102.
9
➀ Get/Set
Assembly
Word 2 Param
USINT 0 to 88 0
Bulletin 160 SSC Interface parameter number whose value is
used as the third word in Input Assembly 102.
10
➀ Get/Set
Assembly
Word 3 Param
USINT 0 to 88 0
Bulletin 160 SSC Interface parameter number whose value is
used as the fourth word in Input Assembly 102.
11 Get/Set DN Idle Mode BOOL 0 to 1 0 0 = Stop, 1 = Hold Last State.
12 Get
DN Software
Version
WORD 0.00 to 10.00 2.00 Indicates the software version of the DeviceNet option.
13 Get/Set
DN Change of
State Mask
WORD 0 to 0xFFFF 0xFFFF
A 16 bit mask used to enable automatic change of state
messages.
14 Get/Set
Local Return
Mode
BYTE 0 to 5 0
Sets the input mode the drive will use when transitioning from
network to local control.
15 Get
DeviceNet DIP
Switches
BYTE 0 to 255 Current DIP switch settings on the 160-DN2 module.
Service
Code
Implemented for:
Service
Name
Class Instance
0x0E No Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single