Reference Manual User Manual
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
14 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
18. EMC
The unit is suitable for applications in industrial environments as well as in residencial, commercial and light industry
environment without any restrictions. The CE Mark indicates conformance with EMC guideline 89/336/EC, 93/68/EC and
2004/108/EC and the low-voltage directive (LVD) 73/23/EC, 93/68/EC and 2006/95/EC.
A detailed EMC report is avalaible upon request.
EMC Immunity
EN 61000-6-1, EN 61000-6-2 Generic standards
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV
15kV
Criterion A*)
Criterion A*)
Electromagnetic RF eld EN 61000-4-3 80MHz-2.7GHz 10V/m Criterion A
Fast transients (Burst) EN 61000-4-4 Out- and Input lines
Signal lines **)
2kV
2kV
Criterion A
Criterion A
Surge voltage
EN 61000-4-5 + -
500V
500V
Criterion A
Criterion A
+ -
housing
500V
Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A
*) DIN rail earthed
**) Tested with coupling clamp.
EMC Emission
EN 61000-6-3 and EN 61000-6-4 Generic standards
Conducted emission EN 55022 Input lines Class B*)
Class B*)
Radiated emission EN 55011, EN 55022 Class B
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
*) Informative measurement with voltage probe
Switching frequency
The DC-UPS has three converters with three different switching frequencies included.
Switching frequency of boost converter 100kHz Constant frequency
Switching frequency of electronic output current limitation 78kHz Constant frequency
Switching frequency of battery charger 19.5kHz Constant frequency
Output
Input
+
-
EN 55022
Output lines