Reference Manual User Manual
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
16 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
Product certification information (including Certificates and Declarations of Conformity) can be found at www.ab.com/certifications.
21. Safety
Output voltage SELV IEC/EN 60950-1
PELV EN 60204-1, EN 50178, IEC 60364-4-41
Max. allowed voltage between any input, output or signal pin and ground:
60Vdc or 42.4Vac
Class of protection III PE (Protective Earth) connection is not required.
Isolation resistance > 5MOhm Power port to housing, 500Vdc
Dielectric strength 500Vac Power port to signal port
500Vac Power port / signal port to housing
Touch current (leakage current) The leakage current which is produced by the DC-UPS itself depends on the input
voltage ripple and need to be investigated in the nal application.
For a smooth DC input voltage, the produced leakage current is less than 100
μA.
22. Certications
EC Declaration of
Conformity
Complies with:
- CE EMC directive
- CE Low-voltage directive
UL 508
LISTED E56639 for the use in the U.S.A. (UL 508) and Canada
(C22.2 No. 14-95). Industrial Control Equipment
ISA 12.12.01, CSA
C22.2 No. 213
RECOGNIZED UNDER FILE NUMBER E244404 for use in the U.S.A.
(ISA 12.12.01) and Canada (C22.2 No. 213)
Hazardous Location Class I, Div. 2 - Groups A, B, C, D
GOST R
GOST R certication is applicable for products intended for sale and
use within Russia. See below for link to Certicate.
C-TICK
C-tick compliance is for products intended for sale and use within
the Australian market. See below for the link to the C-tick Declaration
of Conformity.
Marine GL GL (Germanischer Lloyd) classied for marine and offshore
applications. Environmental category: C, EMC2. See below for link
to Certicate.
Marine Rina
RINA (Registro Italiano Navale) certied. See below for the link to
the certicate.
UL 60950-1
RECOGNIZED E168663 for use in the U.S.A. (UL 60950-1)
and Canada (C22.2 No. 60950)
Information Technology Equipment, Level 3
CSA C22.2 No. 213
ISA 12.12.01
CSA Certied under File Number 240020; CERTIFIED for use in the
U.S.A. (ISA 12.12.01) and Canada (C22.2 No. 213)
Hazardous Location Class I, Div. 2 - Groups A, B, C, D