All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
18 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
25. Installation Notes
Mounting:
The power terminal shall be located on top of the unit. An appropriate electrical and re end-product enclosure should
be considered in the end use application.
Cooling:
Convection cooled, no forced air cooling required. Do not obstruct air ow!
Installation clearances:
40mm on top, 20mm on the bottom, 5mm on the left side are recommended when loaded
permanently with more than 5A. Do not place heat sources next to the 1606-XLS240-UPSE
since it can inuence the function of rthe internal temperature sensor. Keep a minimum of
15mm from the adjacent device.
Risk of electrical shock, re, personal injury or death!
Turn power o and disconnect battery fuse before working on the DC-UPS. Protect against inadvertently re-powering.
Make sure the wiring is correct by following all local and national codes. Do not open, modify or repair the unit. Use
caution to prevent any foreign object from penetrating in the housing. Do not use in wet locations or in areas where
moisture and condensation can be expected.
Service parts:
The unit does not contain any service parts. The tripping of an internal fuse is caused by an internal fault. If damage or
malfunctioning should occur during operation, immediately turn power o and send unit to the factory for inspection.
Wiring and installation instructions:
(1) Connect the power supply to the input terminals of the DC-UPS.
(2)
Connect the battery to the battery terminals of the DC-UPS. Do not install the battery in airtight housings or cabinets.
(3) Connect the buered load to the output terminals of the DC-UPS. The output is decoupled from the input allowing load
(4)
Install the fuse upon completion of the wiring.
Fig. 25-1 Typical wiring diagram
24V
Power
Supply
+
-
NLPE
DC-UPS
1606-XLS240
-UPSE
24V
IN
24V
OUT
12V
BAT
+
-
+
-
+
-
12V
Battery
Module
+
-
Buffered
Load
+
-
Non-
buffered
Load
+
-
24V
buffered
branches
24V
Non-bufferd
branches
The battery should be installed according to EN50272-2, which includes sucient ventilation. Batteries store energy and
must be protected against energy hazards. Use a 30A battery fuse type ATO® 257 30 (Littelfuse) or similar in the battery path.
The battery fuse protects the wires between the battery and the DC-UPS. It also allows the disconnection of the battery from
the DC-UPS which we recommend when working on the battery or DC-UPS. Disconnect battery fuse before connecting the
battery. Please note: Excessively long or short wires between the DC-UPS and battery may shorten the buer time or result
in a malfunction of the DC-UPS. Do not use wires smaller than 2.5mm² (or 12AWG) and no longer than 2x1.5m (cord length
1.5m). Avoid voltage drops on this connection.
circuits to be easily split into buered and non-buered sections. Noncritical loads can be connected directly to the|
power supply and will not be buered. The energy of the battery can then be used in the circuits that require buering.