Reference Manual User Manual

All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
6 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
7. Output in Buer Mode
If the input voltage falls below a certain value (transfer threshold level), the DC-UPS starts buering without any
interruption or voltage dips. Buering is possible even if battery not fully charged.
Output voltage in buer mode
nom. DC 24V Output voltage is stabilized and independent from
battery voltage
22.45V ±1%, at no load,
22.25V ±1%, at 10A output current
Transfer threshold for buering
typ. 80mV higher than the output voltage in buer mode
Ripple and noise voltage max. 20mVpp 20Hz to 20MHz, 50Ohm
Output current nom. 10A Continuously allowed
15A < 5s with full output voltage *)
Short-circuit current
min. 17.9A Load impedance 100mOhm **)
max. 21A Load impedance 100mOhm **)
*) If the output current is in the range between 10A and 15A for longer than 5s, a hardware controlled reduction of the
maximal output current to 10A occurs. If the 10A are not suci
ent to maintain the 24V, buering stops after another 5s.
Buering will again be possible as soon as the input voltage recovers.
**) If the nominal output voltage cannot be maintained in buer mode, the DC-UPS switches o after 5s to save battery
capacity.
Fig. 7-1 Buering transition, denitions
Buffer mode
Output
voltage
24V
28V
Input
voltage
t
t
Transfer
threshold
5
0
0
m
s
/
D
I
V
0
V
O
u
t
p
u
t
V
o
l
t
a
g
e
I
n
p
u
t
V
o
l
t
a
g
e
2
4
V
2
2
.
2
5
V
a
t
1
0
A
2
4
V
Fig. 7-3 Available output current in
buer mode
Fig. 7-4 Output voltage vs. output current
in buer mode, typ.
Output Current
0
05 Sec.
15A
10A
Time
5A
BonusPower
Output Voltage
A
B
C
Continuously available
Available for 5s then auto switching to curve
Buffering will stop after 5s
D
0
0
5101520
5
10
15
25V
20
25A
Output
Current
A B
CD
D
Buffering will stop after 5s